Implementation Grant Funding Opportunity Open
IMPORTANT: The grant program operates on a rolling basis and applications may be submitted at any time, with quarterly reviews.
Learn More
Implementation Grant Funding Opportunity Open
Qualifying* small and medium-sized US manufacturers, that received IAC or Combined Heat and Power Technical Assistance Partnership assessments between 2018 and 2024, can now apply for grants for implementation of assessment recommendations up 50% of qualifying* project costs with a maximum of $300,000 per manufacturer.
IMPORTANT: The grant program now operates on a rolling basis and applications may be submitted at any time through the year, with quarterly reviews.
*See Full Grant Solicitation for full qualification and selection details.
IAC Center | San Francisco State University |
---|---|
Assessment Year | 1998 |
Principal Product | Canned Vegetables and Fruits |
NAICS | n/a |
SIC | 2030 - |
Sales | $10,000,000-$50,000,000 |
# of Employees | 260 |
Plant Area (Sq.Ft.) | 375,000 |
Annual Production | 110,000,000 Pounds |
Production Hrs. Annual | 4,800 |
Location (State) | CA |
Source | Yearly Cost | Usage | Unit | Unit Cost |
---|---|---|---|---|
Electricity Usage | $250,452 | 8,778,136 | kWh | $0.03 |
Electricity Demand | $140,514 | 16,651 | kW-months/year | $8.44 |
Natural Gas | $102,911 | 36,754 | MMBtu | $2.80 |
TOTAL ENERGY COSTS | $752,377 | |||
RECOMMENDED SAVINGS* | $174,532 | *Non-energy impacts included in savings. See recommendations below |
||
IMPLEMENTED SAVINGS* | $63,773 |
#|Description |
Savings Cost |
Status | Electricity Usage | Electricity Demand | Electricity Fees | Natural Gas | Water Disposal | Solid Waste (non-haz) | Personnel Changes | Electricity Usage | Electricity Demand | Electricity Fees | Natural Gas | Water Disposal | Solid Waste (non-haz) | Personnel Changes | |||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||
---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|
$ | kWh | $ | kW-months/year | $ | $ | $ | MMBtu | $ | Tgal | $ | lb | $ | $ | ||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||
01: 2.2523 REDUCE INFILTRATION TO REFRIGERATED AREAS; ISOLATE HOT EQUIPMENT FROM REFRIGERATED AREAS |
Savings: $1,575 Cost: - |
$1,575 | 48,945 | - | - | - | - | - | - | - | - | - | - | - | - |
$1,575 48,945 kWh |
- - kW-months/year |
- - $ |
- - MMBtu |
- - Tgal |
- - lb |
- - $ |
|||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||
02: 2.3132 RECHARGE BATTERIES ON DURING OFF-PEAK DEMAND PERIODS |
Savings: $6,958 Cost: - |
- | - | - | - | $6,958 | - | - | - | - | - | - | - | - | - |
- - kWh |
- - kW-months/year |
$6,958 - $ |
- - MMBtu |
- - Tgal |
- - lb |
- - $ |
|||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||
03: 2.2135 REPAIR AND ELIMINATE STEAM LEAKS |
Savings: $2,548 Cost: $600 |
- | - | - | - | - | - | $2,548 | 1,066 | - | - | - | - | - | - |
- - kWh |
- - kW-months/year |
- - $ |
$2,548 1,066 MMBtu |
- - Tgal |
- - lb |
- - $ |
|||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||
04: 2.4239 ELIMINATE OR REDUCE COMPRESSED AIR USAGE |
Savings: $382 Cost: $150 |
$257 | 7,620 | $125 | 15 | - | - | - | - | - | - | - | - | - | - |
$257 7,620 kWh |
$125 15 kW-months/year |
- - $ |
- - MMBtu |
- - Tgal |
- - lb |
- - $ |
|||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||
05: 2.7135 INSTALL OCCUPANCY SENSORS |
Savings: $2,965 Cost: $4,440 |
$1,935 | 56,565 | $1,030 | 122 | - | - | - | - | - | - | - | - | - | - |
$1,935 56,565 kWh |
$1,030 122 kW-months/year |
- - $ |
- - MMBtu |
- - Tgal |
- - lb |
- - $ |
|||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||
06: 2.4133 USE MOST EFFICIENT TYPE OF ELECTRIC MOTORS |
Savings: $2,334 Cost: $3,981 |
$1,318 | 38,394 | $1,016 | 120 | - | - | - | - | - | - | - | - | - | - |
$1,318 38,394 kWh |
$1,016 120 kW-months/year |
- - $ |
- - MMBtu |
- - Tgal |
- - lb |
- - $ |
|||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||
07: 2.4146 USE ADJUSTABLE FREQUENCY DRIVE OR MULTIPLE SPEED MOTORS ON EXISTING SYSTEM |
Savings: $3,553 Cost: $11,064 |
$1,773 | 51,876 | $1,024 | 122 | - | - | - | - | $756 | 525,000 | - | - | - | - |
$1,773 51,876 kWh |
$1,024 122 kW-months/year |
- - $ |
- - MMBtu |
$756 525,000 Tgal |
- - lb |
- - $ |
|||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||
08: 2.7134 USE PHOTOCELL CONTROLS |
Savings: $7,051 Cost: $27,750 |
$4,722 | 137,749 | $2,329 | 276 | - | - | - | - | - | - | - | - | - | - |
$4,722 137,749 kWh |
$2,329 276 kW-months/year |
- - $ |
- - MMBtu |
- - Tgal |
- - lb |
- - $ |
|||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||
09: 2.7142 UTILIZE HIGHER EFFICIENCY LAMPS AND/OR BALLASTS |
Savings: $5,405 Cost: $21,900 |
$3,448 | 100,821 | $1,957 | 232 | - | - | - | - | - | - | - | - | - | - |
$3,448 100,821 kWh |
$1,957 232 kW-months/year |
- - $ |
- - MMBtu |
- - Tgal |
- - lb |
- - $ |
|||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||
10: 3.5313 INCREASE AMOUNT OF WASTE RECOVERED FOR RESALE |
Savings: $7,480 Cost: $550 |
- | - | - | - | - | - | - | - | - | - | $7,480 | 106,482 | - | - |
- - kWh |
- - kW-months/year |
- - $ |
- - MMBtu |
- - Tgal |
$7,480 106,482 lb |
- - $ |
|||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||
11: 3.4155 METER WASTE WATER |
Savings: $91,785 Cost: $180,000 |
- | - | - | - | - | - | - | - | $91,785 | - | - | - | - | - |
- - kWh |
- - kW-months/year |
- - $ |
- - MMBtu |
$91,785 - Tgal |
- - lb |
- - $ |
|||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||
12: 4.214 PURCHASE APPROPRIATELY SIZED MATERIAL |
Savings: $39,680 Cost: $15,000 |
- | - | - | - | - | - | - | - | - | - | - | - | $39,680 | - |
- - kWh |
- - kW-months/year |
- - $ |
- - MMBtu |
- - Tgal |
- - lb |
$39,680 - $ |
|||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||
13: 4.446 AUTOMATE FINISHING PROCESS |
Savings: $2,816 Cost: $5,000 |
- | - | - | - | - | - | - | - | - | - | - | - | $2,816 | - |
- - kWh |
- - kW-months/year |
- - $ |
- - MMBtu |
- - Tgal |
- - lb |
$2,816 - $ |
|||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||
TOTAL RECOMMENDED |
Savings: $174,532 Cost: $270,435 |
$15,028 | 441,970 | $7,481 | 887 | $6,958 | - | $2,548 | 1,066 | $92,541 | 525,000 | $7,480 | 106,482 | $42,496 | - | $15,028 441,970 kWh |
$7,481 887 kW-months/year |
$6,958 - $ |
$2,548 1,066 MMBtu |
$92,541 525,000 Tgal |
$7,480 106,482 lb |
$42,496 - $ |
|||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||
TOTAL IMPLEMENTED |
Savings: $63,773 Cost: $25,281 |
$3,150 | 94,959 | $1,141 | 135 | $6,958 | - | $2,548 | 1,066 | - | - | $7,480 | 106,482 | $42,496 | - | $3,150 94,959 kWh |
$1,141 135 kW-months/year |
$6,958 - $ |
$2,548 1,066 MMBtu |
- - Tgal |
$7,480 106,482 lb |
$42,496 - $ |
|||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||
Savings Cost |
$ | kWh | $ | kW-months/year | $ | $ | $ | MMBtu | $ | Tgal | $ | lb | $ | $ | |||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||
Electricity Usage | Electricity Demand | Electricity Fees | Natural Gas | Water Disposal | Solid Waste (non-haz) | Personnel Changes | Electricity Usage | Electricity Demand | Electricity Fees | Natural Gas | Water Disposal | Solid Waste (non-haz) | Personnel Changes |