Qualifying* small and medium-sized US manufacturers, that received IAC or Combined Heat and Power Technical Assistance Partnership assessments between 2018 and 2024, can now apply for grants for implementation of assessment recommendations up 50% of qualifying* project costs with a maximum of $300,000 per manufacturer.
IMPORTANT: The grant program now operates on a rolling basis and applications may be submitted at any time through the year, with quarterly reviews.
*See Full Grant Solicitation for full qualification and selection details.
IAC Center | Syracuse University |
---|---|
Assessment Year | 2005 |
Principal Product | Ceramic Capacitors |
NAICS | 334416 - Capacitor, Resistor, Coil, Transformer, and Other Inductor Manufacturing |
SIC | 3675 - Electronic Capacitors |
Sales | $50,000,000-$100,000,000 |
# of Employees | 160 |
Plant Area (Sq.Ft.) | 121,200 |
Annual Production | 51,000,000 Pieces |
Production Hrs. Annual | 8,760 |
Location (State) | NY |
Source | Yearly Cost | Usage | Unit | Unit Cost |
---|---|---|---|---|
Electricity Usage | $230,991 | 3,903,703 | kWh | $0.06 |
Electricity Demand | $160,373 | 7,145 | kW-months/year | $22.45 |
Electricity Fees | $7,285 | - | $ | - |
Natural Gas | $141,578 | 16,189 | MMBtu | $8.75 |
TOTAL ENERGY COSTS | $540,227 | |||
RECOMMENDED SAVINGS* | $154,315 | *Non-energy impacts included in savings. See recommendations below |
||
IMPLEMENTED SAVINGS* | $47,585 |
#|Description |
Savings Cost |
Status | Electricity Usage | Electricity Demand | One-time Revenue or Avoided Cost | Electricity Usage | Electricity Demand | One-time Revenue or Avoided Cost | |||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||
---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|
$ | kWh | $ | kW-months/year | $ | $ | ||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||
01: 2.8114 CHANGE RATE SCHEDULES OR OTHER CHANGES IN UTILITY SERVICE |
Savings: $15,621 Cost: - |
- | - | - | - | $15,621 | - |
- - kWh |
- - kW-months/year |
$15,621 - $ |
|||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||
02: 2.4231 REDUCE THE PRESSURE OF COMPRESSED AIR TO THE MINIMUM REQUIRED |
Savings: $7,400 Cost: - |
$3,628 | 61,496 | $3,772 | 168 | - | - |
$3,628 61,496 kWh |
$3,772 168 kW-months/year |
- - $ |
|||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||
03: 2.4111 UTILIZE ENERGY-EFFICIENT BELTS AND OTHER IMPROVED MECHANISMS |
Savings: $2,356 Cost: - |
$1,279 | 21,680 | $1,077 | 48 | - | - |
$1,279 21,680 kWh |
$1,077 48 kW-months/year |
- - $ |
|||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||
04: 2.4221 INSTALL COMPRESSOR AIR INTAKES IN COOLEST LOCATIONS |
Savings: $15,286 Cost: $502 |
$7,473 | 126,670 | $7,813 | 348 | - | - |
$7,473 126,670 kWh |
$7,813 348 kW-months/year |
- - $ |
|||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||
05: 2.4236 ELIMINATE LEAKS IN INERT GAS AND COMPRESSED AIR LINES/ VALVES |
Savings: $3,948 Cost: $721 |
$1,927 | 32,675 | $2,021 | 90 | - | - |
$1,927 32,675 kWh |
$2,021 90 kW-months/year |
- - $ |
|||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||
06: 2.4146 USE ADJUSTABLE FREQUENCY DRIVE OR MULTIPLE SPEED MOTORS ON EXISTING SYSTEM |
Savings: $40,969 Cost: $38,400 |
$22,336 | 378,593 | $18,633 | 830 | - | - |
$22,336 378,593 kWh |
$18,633 830 kW-months/year |
- - $ |
|||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||
07: 2.7122 DISCONNECT BALLASTS |
Savings: $6,107 Cost: $5,363 |
$4,019 | 68,118 | $2,088 | 93 | - | - |
$4,019 68,118 kWh |
$2,088 93 kW-months/year |
- - $ |
|||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||
08: 2.7135 INSTALL OCCUPANCY SENSORS |
Savings: $1,137 Cost: $1,726 |
$1,137 | 19,272 | - | - | - | - |
$1,137 19,272 kWh |
- - kW-months/year |
- - $ |
|||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||
09: 2.7142 UTILIZE HIGHER EFFICIENCY LAMPS AND/OR BALLASTS |
Savings: $694 Cost: $1,262 |
$233 | 3,942 | $112 | 5 | $349 | - |
$233 3,942 kWh |
$112 5 kW-months/year |
$349 - $ |
|||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||
10: 2.6211 CONSERVE ENERGY BY EFFICIENT USE OF VENDING MACHINES |
Savings: $276 Cost: $509 |
$186 | 3,150 | $90 | 4 | - | - |
$186 3,150 kWh |
$90 4 kW-months/year |
- - $ |
|||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||
11: 3.1191 CHANGE PROCEDURES / EQUIPMENT / OPERATING CONDITIONS |
Savings: $53,360 Cost: $111,859 |
- | - | - | - | $53,360 | - |
- - kWh |
- - kW-months/year |
$53,360 - $ |
|||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||
12: 2.7131 ADD AREA LIGHTING SWITCHES |
Savings: $4,267 Cost: $10,645 |
$4,267 | 72,331 | - | - | - | - |
$4,267 72,331 kWh |
- - kW-months/year |
- - $ |
|||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||
13: 2.3212 OPTIMIZE PLANT POWER FACTOR |
Savings: $2,894 Cost: $17,500 |
- | - | - | - | $2,894 | - |
- - kWh |
- - kW-months/year |
$2,894 - $ |
|||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||
TOTAL RECOMMENDED |
Savings: $154,315 Cost: $188,487 |
$46,485 | 787,927 | $35,606 | 1,586 | $72,224 | - | $46,485 787,927 kWh |
$35,606 1,586 kW-months/year |
$72,224 - $ |
|||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||
TOTAL IMPLEMENTED |
Savings: $47,585 Cost: $17,231 |
$18,965 | 321,474 | $12,999 | 579 | $15,621 | - | $18,965 321,474 kWh |
$12,999 579 kW-months/year |
$15,621 - $ |
|||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||
Savings Cost |
$ | kWh | $ | kW-months/year | $ | $ | |||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||
Electricity Usage | Electricity Demand | One-time Revenue or Avoided Cost | Electricity Usage | Electricity Demand | One-time Revenue or Avoided Cost |