Implementation Grant Funding Opportunity Open
IMPORTANT: The grant program operates on a rolling basis and applications may be submitted at any time, with quarterly reviews.
Learn More
Implementation Grant Funding Opportunity Open
Qualifying* small and medium-sized US manufacturers, that received IAC or Combined Heat and Power Technical Assistance Partnership assessments between 2018 and 2024, can now apply for grants for implementation of assessment recommendations up 50% of qualifying* project costs with a maximum of $300,000 per manufacturer.
IMPORTANT: The grant program now operates on a rolling basis and applications may be submitted at any time through the year, with quarterly reviews.
*See Full Grant Solicitation for full qualification and selection details.
IAC Center | University of Florida |
---|---|
Assessment Year | 2022 |
Principal Product | Wastewater Treatment |
NAICS | 221320 - Sewage Treatment Facilities |
SIC | 4952 - Sewerage Systems |
Sales | $1,000,000-$5,000,000 |
# of Employees | 15 |
Plant Area (Sq.Ft.) | 333,900 |
Annual Production | 4,999,150 Thousand Gallons |
Production Hrs. Annual | 8,760 |
Location (State) | FL |
Source | Yearly Cost | Usage | Unit | Unit Cost |
---|---|---|---|---|
Electricity Usage | $640,333 | 16,696,800 | kWh | $0.04 |
Electricity Demand | $243,999 | 31,652 | kW-months/year | $7.71 |
Electricity Fees | $25,924 | - | $ | - |
TOTAL ENERGY COSTS | $910,256 | |||
RECOMMENDED SAVINGS* | $206,068 | *Non-energy impacts included in savings. See recommendations below |
||
IMPLEMENTED SAVINGS* | $184,778 |
#|Description |
Savings Cost |
Status | Electricity Usage | Electricity Demand | Primary Raw Material | Ancillary Material Cost | Electricity Usage | Electricity Demand | Primary Raw Material | Ancillary Material Cost | |||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||
---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|
$ | kWh | $ | kW-months/year | $ | $ | $ | $ | ||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||
01: 2.3191 USE DEMAND CONTROLLER OR LOAD SHEDDER |
Savings: $61,494 Cost: $87,677 |
$44,413 | 1,168,776 | $17,081 | 2,216 | - | - | - | - |
$44,413 1,168,776 kWh |
$17,081 2,216 kW-months/year |
- - $ |
- - $ |
||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||
02: 2.4112 INSTALL SOFT-START TO ELIMINATE NUISANCE TRIPS |
Savings: $15,702 Cost: $33,667 |
$15,702 | 413,200 | - | - | - | - | - | - |
$15,702 413,200 kWh |
- - kW-months/year |
- - $ |
- - $ |
||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||
03: 2.6231 UTILIZE CONTROLS TO OPERATE EQUIPMENT ONLY WHEN NEEDED |
Savings: $12,945 Cost: $20,214 |
$12,945 | 340,671 | - | - | - | - | - | - |
$12,945 340,671 kWh |
- - kW-months/year |
- - $ |
- - $ |
||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||
04: 2.4133 USE MOST EFFICIENT TYPE OF ELECTRIC MOTORS |
Savings: $12,034 Cost: $32,610 |
$7,885 | 207,507 | $4,149 | 538 | - | - | - | - |
$7,885 207,507 kWh |
$4,149 538 kW-months/year |
- - $ |
- - $ |
||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||
05: 2.7142 UTILIZE HIGHER EFFICIENCY LAMPS AND/OR BALLASTS |
Savings: $11,674 Cost: $35,369 |
$7,061 | 185,817 | $4,613 | 598 | - | - | - | - |
$7,061 185,817 kWh |
$4,613 598 kW-months/year |
- - $ |
- - $ |
||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||
06: 2.7135 INSTALL OCCUPANCY SENSORS |
Savings: $4,026 Cost: $12,390 |
$4,026 | 105,954 | - | - | - | - | - | - |
$4,026 105,954 kWh |
- - kW-months/year |
- - $ |
- - $ |
||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||
07: 4.661 LEVEL ZERO – INSTALL CONTROL SYSTEMS FOR EXISTING EQUIPMENT |
Savings: $63,448 Cost: $10,000 |
$63,448 | 1,669,680 | - | - | - | - | - | - |
$63,448 1,669,680 kWh |
- - kW-months/year |
- - $ |
- - $ |
||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||
08: 4.446 AUTOMATE FINISHING PROCESS |
Savings: $17,264 Cost: $3,564 |
- | - | - | - | - | - | $17,264 | - |
- - kWh |
- - kW-months/year |
- - $ |
$17,264 - $ |
||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||
09: 4.662 LEVEL ONE – ADD COMMUNICATION USING IIOT DEVICES TO EXISTING CONTROL SYSTEM TO MODIFY OPERATIONS |
Savings: $7,481 Cost: - |
- | - | - | - | $7,481 | - | - | - |
- - kWh |
- - kW-months/year |
$7,481 - $ |
- - $ |
||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||
TOTAL RECOMMENDED |
Savings: $206,068 Cost: $235,491 |
$155,480 | 4,091,605 | $25,843 | 3,352 | $7,481 | - | $17,264 | - | $155,480 4,091,605 kWh |
$25,843 3,352 kW-months/year |
$7,481 - $ |
$17,264 - $ |
||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||
TOTAL IMPLEMENTED |
Savings: $184,778 Cost: $219,537 |
$151,454 | 3,985,651 | $25,843 | 3,352 | $7,481 | - | - | - | $151,454 3,985,651 kWh |
$25,843 3,352 kW-months/year |
$7,481 - $ |
- - $ |
||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||
Savings Cost |
$ | kWh | $ | kW-months/year | $ | $ | $ | $ | |||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||
Electricity Usage | Electricity Demand | Primary Raw Material | Ancillary Material Cost | Electricity Usage | Electricity Demand | Primary Raw Material | Ancillary Material Cost |