Qualifying* small and medium-sized US manufacturers, that received IAC or Combined Heat and Power Technical Assistance Partnership assessments between 2018 and 2024, can now apply for grants for implementation of assessment recommendations up 50% of qualifying* project costs with a maximum of $300,000 per manufacturer.
IMPORTANT: The grant program now operates on a rolling basis and applications may be submitted at any time through the year, with quarterly reviews.
*See Full Grant Solicitation for full qualification and selection details.
IAC Center | University of Florida |
---|---|
Assessment Year | 2024 |
Principal Product | Plastic Containers |
NAICS | 326199 - All Other Plastics Product Manufacturing |
SIC | 3089 - Plastics Products, Nec |
Sales | $50,000,000-$100,000,000 |
# of Employees | 100 |
Plant Area (Sq.Ft.) | 200,000 |
Annual Production | 1,700,000,000 Units |
Production Hrs. Annual | 8,760 |
Location (State) | FL |
Source | Yearly Cost | Usage | Unit | Unit Cost |
---|---|---|---|---|
Electricity Usage | $3,015,160 | 49,363,264 | kWh | $0.06 |
Electricity Demand | $752,096 | 87,622 | kW-months/year | $8.58 |
Electricity Fees | $383,259 | - | $ | - |
TOTAL ENERGY COSTS | $4,150,515 | |||
RECOMMENDED SAVINGS* | $2,392,478 | *Non-energy impacts included in savings. See recommendations below |
||
IMPLEMENTED SAVINGS* | - |
#|Description |
Savings Cost |
Status | Electricity Usage | Electricity Demand | Personnel Changes | Administrative Changes | Ancillary Material Cost | Electricity Usage | Electricity Demand | Personnel Changes | Administrative Changes | Ancillary Material Cost | |||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||
---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|
$ | kWh | $ | kW-months/year | $ | $ | $ | $ | $ | $ | ||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||
01: 2.2623 MINIMIZE CONDENSER COOLING WATER TEMPERATURE |
Savings: $942,391 Cost: $22,400 |
$942,391 | 15,449,026 | - | - | - | - | - | - | - | - |
$942,391 15,449,026 kWh |
- - kW-months/year |
- - $ |
- - $ |
- - $ |
|||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||
02: 2.4146 USE ADJUSTABLE FREQUENCY DRIVE OR MULTIPLE SPEED MOTORS ON EXISTING SYSTEM |
Savings: $500,050 Cost: $518,990 |
$500,050 | 8,197,549 | - | - | - | - | - | - | - | - |
$500,050 8,197,549 kWh |
- - kW-months/year |
- - $ |
- - $ |
- - $ |
|||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||
03: 2.3191 USE DEMAND CONTROLLER OR LOAD SHEDDER |
Savings: $263,426 Cost: $265,574 |
$210,781 | 3,455,428 | $52,645 | 6,134 | - | - | - | - | - | - |
$210,781 3,455,428 kWh |
$52,645 6,134 kW-months/year |
- - $ |
- - $ |
- - $ |
|||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||
04: 2.6231 UTILIZE CONTROLS TO OPERATE EQUIPMENT ONLY WHEN NEEDED |
Savings: $106,816 Cost: $25,400 |
$106,816 | 1,751,090 | - | - | - | - | - | - | - | - |
$106,816 1,751,090 kWh |
- - kW-months/year |
- - $ |
- - $ |
- - $ |
|||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||
05: 2.4112 INSTALL SOFT-START TO ELIMINATE NUISANCE TRIPS |
Savings: $92,260 Cost: $61,871 |
$92,260 | 1,512,463 | - | - | - | - | - | - | - | - |
$92,260 1,512,463 kWh |
- - kW-months/year |
- - $ |
- - $ |
- - $ |
|||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||
06: 2.9114 USE SOLAR HEAT TO MAKE ELECTRICTY |
Savings: $73,600 Cost: $322,608 |
$40,641 | 666,250 | $32,959 | 3,840 | - | - | - | - | - | - |
$40,641 666,250 kWh |
$32,959 3,840 kW-months/year |
- - $ |
- - $ |
- - $ |
|||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||
07: 2.4224 UPGRADE CONTROLS ON COMPRESSORS |
Savings: $47,434 Cost: - |
$47,434 | 777,600 | - | - | - | - | - | - | - | - |
$47,434 777,600 kWh |
- - kW-months/year |
- - $ |
- - $ |
- - $ |
|||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||
08: 2.4133 USE MOST EFFICIENT TYPE OF ELECTRIC MOTORS |
Savings: $31,281 Cost: $10,800 |
$26,226 | 429,932 | $5,055 | 589 | - | - | - | - | - | - |
$26,226 429,932 kWh |
$5,055 589 kW-months/year |
- - $ |
- - $ |
- - $ |
|||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||
09: 2.4321 UPGRADE OBSOLETE EQUIPMENT |
Savings: $15,235 Cost: $68,900 |
$10,985 | 180,090 | - | - | - | - | $4,250 | - | - | - |
$10,985 180,090 kWh |
- - kW-months/year |
- - $ |
$4,250 - $ |
- - $ |
|||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||
10: 2.7142 UTILIZE HIGHER EFFICIENCY LAMPS AND/OR BALLASTS |
Savings: $8,664 Cost: $22,804 |
$7,212 | 118,237 | $1,452 | 169 | - | - | - | - | - | - |
$7,212 118,237 kWh |
$1,452 169 kW-months/year |
- - $ |
- - $ |
- - $ |
|||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||
11: 2.7141 LOWER LIGHT FIXTURES IN HIGH CEILING AREAS |
Savings: $5,877 Cost: $6,200 |
$4,927 | 80,767 | $950 | 111 | - | - | - | - | - | - |
$4,927 80,767 kWh |
$950 111 kW-months/year |
- - $ |
- - $ |
- - $ |
|||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||
12: 2.4111 UTILIZE ENERGY-EFFICIENT BELTS AND OTHER IMPROVED MECHANISMS |
Savings: $4,329 Cost: - |
$3,976 | 65,185 | - | - | $220 | - | - | - | $133 | - |
$3,976 65,185 kWh |
- - kW-months/year |
$220 - $ |
- - $ |
$133 - $ |
|||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||
13: 4.661 LEVEL ZERO – INSTALL CONTROL SYSTEMS FOR EXISTING EQUIPMENT |
Savings: $301,115 Cost: $60,000 |
$301,115 | 4,936,326 | - | - | - | - | - | - | - | - |
$301,115 4,936,326 kWh |
- - kW-months/year |
- - $ |
- - $ |
- - $ |
|||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||
TOTAL RECOMMENDED |
Savings: $2,392,478 Cost: $1,385,547 |
$2,294,814 | 37,619,943 | $93,061 | 10,842 | $220 | - | $4,250 | - | $133 | - | $2,294,814 37,619,943 kWh |
$93,061 10,842 kW-months/year |
$220 - $ |
$4,250 - $ |
$133 - $ |
|||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||
TOTAL IMPLEMENTED |
Savings: - Cost: - |
- | - | - | - | - | - | - | - | - | - | - - kWh |
- - kW-months/year |
- - $ |
- - $ |
- - $ |
|||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||
Savings Cost |
$ | kWh | $ | kW-months/year | $ | $ | $ | $ | $ | $ | |||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||
Electricity Usage | Electricity Demand | Personnel Changes | Administrative Changes | Ancillary Material Cost | Electricity Usage | Electricity Demand | Personnel Changes | Administrative Changes | Ancillary Material Cost |