IAC Center | University of Kentucky |
---|---|
Assessment Year | 2019 |
Principal Product | Cut and sewn apparel |
NAICS | 315210 - Cut and Sew Apparel Contractors |
SIC | 2311 - Men's and Boys' Suits, Coats, and Overcoats |
Sales | $10,000,000-$50,000,000 |
# of Employees | 120 |
Plant Area (Sq.Ft.) | 60,000 |
Annual Production | 400,000 Units |
Production Hrs. Annual | 2,138 |
Location (State) | KY |
Source | Yearly Cost | Usage | Unit | Unit Cost |
---|---|---|---|---|
Electricity Usage | $60,766 | 859,520 | kWh | $0.07 |
Electricity Demand | $27,076 | 3,531 | kW-months/year | $7.67 |
Electricity Fees | $2,637 | - | $ | - |
Natural Gas | $11,741 | 1,363 | MMBtu | $8.61 |
TOTAL ENERGY COSTS | $118,784 | |||
RECOMMENDED SAVINGS* | $26,811 | *Non-energy impacts included in savings. See recommendations below |
||
IMPLEMENTED SAVINGS* | $25,226 |
#|Description |
Savings Cost |
Status | Electricity Usage | Electricity Demand | Electricity Fees | Natural Gas | Electricity Usage | Electricity Demand | Electricity Fees | Natural Gas | |||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||
---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|
$ | kWh | $ | kW-months/year | $ | $ | $ | MMBtu | ||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||
01: 2.4221 INSTALL COMPRESSOR AIR INTAKES IN COOLEST LOCATIONS |
Savings: $260 Cost: $825 |
$260 | 3,660 | - | - | - | - | - | - |
$260 3,660 kWh |
- - kW-months/year |
- - $ |
- - MMBtu |
||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||
02: 2.4231 REDUCE THE PRESSURE OF COMPRESSED AIR TO THE MINIMUM REQUIRED |
Savings: $3,079 Cost: $1,308 |
$1,744 | 24,570 | $1,335 | 174 | - | - | - | - |
$1,744 24,570 kWh |
$1,335 174 kW-months/year |
- - $ |
- - MMBtu |
||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||
03: 2.4231 REDUCE THE PRESSURE OF COMPRESSED AIR TO THE MINIMUM REQUIRED |
Savings: $320 Cost: - |
$200 | 2,815 | $120 | 16 | - | - | - | - |
$200 2,815 kWh |
$120 16 kW-months/year |
- - $ |
- - MMBtu |
||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||
04: 2.4236 ELIMINATE LEAKS IN INERT GAS AND COMPRESSED AIR LINES/ VALVES |
Savings: $2,436 Cost: $2,510 |
$1,516 | 21,349 | $920 | 120 | - | - | - | - |
$1,516 21,349 kWh |
$920 120 kW-months/year |
- - $ |
- - MMBtu |
||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||
05: 2.7224 REDUCE SPACE CONDITIONING DURING NON-WORKING HOURS |
Savings: $4,090 Cost: $640 |
$4,090 | 57,600 | - | - | - | - | - | - |
$4,090 57,600 kWh |
- - kW-months/year |
- - $ |
- - MMBtu |
||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||
06: 2.2437 RECOVER WASTE HEAT FROM EQUIPMENT |
Savings: $1,464 Cost: - |
- | - | - | - | - | - | $1,464 | 170 |
- - kWh |
- - kW-months/year |
- - $ |
$1,464 170 MMBtu |
||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||
07: 2.7134 USE PHOTOCELL CONTROLS |
Savings: $180 Cost: $170 |
$180 | 2,540 | - | - | - | - | - | - |
$180 2,540 kWh |
- - kW-months/year |
- - $ |
- - MMBtu |
||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||
08: 2.7135 INSTALL OCCUPANCY SENSORS |
Savings: $1,919 Cost: $1,460 |
$1,919 | 27,023 | - | - | - | - | - | - |
$1,919 27,023 kWh |
- - kW-months/year |
- - $ |
- - MMBtu |
||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||
09: 2.7111 REDUCE ILLUMINATION TO MINIMUM NECESSARY LEVELS |
Savings: $1,774 Cost: $941 |
$1,213 | 17,080 | $561 | 73 | - | - | - | - |
$1,213 17,080 kWh |
$561 73 kW-months/year |
- - $ |
- - MMBtu |
||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||
10: 2.7124 MAKE A PRACTICE OF TURNING OFF LIGHTS WHEN NOT NEEDED |
Savings: $63 Cost: $50 |
$63 | 882 | - | - | - | - | - | - |
$63 882 kWh |
- - kW-months/year |
- - $ |
- - MMBtu |
||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||
11: 2.7142 UTILIZE HIGHER EFFICIENCY LAMPS AND/OR BALLASTS |
Savings: $9,240 Cost: $26,497 |
$6,356 | 89,520 | $2,884 | 376 | - | - | - | - |
$6,356 89,520 kWh |
$2,884 376 kW-months/year |
- - $ |
- - MMBtu |
||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||
12: 2.4133 USE MOST EFFICIENT TYPE OF ELECTRIC MOTORS |
Savings: $96 Cost: $31 |
$60 | 839 | $36 | 5 | - | - | - | - |
$60 839 kWh |
$36 5 kW-months/year |
- - $ |
- - MMBtu |
||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||
13: 2.4111 UTILIZE ENERGY-EFFICIENT BELTS AND OTHER IMPROVED MECHANISMS |
Savings: $305 Cost: $33 |
$290 | 4,085 | $15 | 2 | - | - | - | - |
$290 4,085 kWh |
$15 2 kW-months/year |
- - $ |
- - MMBtu |
||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||
14: 2.3212 OPTIMIZE PLANT POWER FACTOR |
Savings: $1,585 Cost: $3,010 |
- | - | - | - | $1,585 | - | - | - |
- - kWh |
- - kW-months/year |
$1,585 - $ |
- - MMBtu |
||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||
TOTAL RECOMMENDED |
Savings: $26,811 Cost: $37,475 |
$17,891 | 251,963 | $5,871 | 765 | $1,585 | - | $1,464 | 170 | $17,891 251,963 kWh |
$5,871 765 kW-months/year |
$1,585 - $ |
$1,464 170 MMBtu |
||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||
TOTAL IMPLEMENTED |
Savings: $25,226 Cost: $34,465 |
$17,891 | 251,963 | $5,871 | 765 | - | - | $1,464 | 170 | $17,891 251,963 kWh |
$5,871 765 kW-months/year |
- - $ |
$1,464 170 MMBtu |
||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||
Savings Cost |
$ | kWh | $ | kW-months/year | $ | $ | $ | MMBtu | |||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||
Electricity Usage | Electricity Demand | Electricity Fees | Natural Gas | Electricity Usage | Electricity Demand | Electricity Fees | Natural Gas |