Qualifying* small and medium-sized US manufacturers, that received IAC or Combined Heat and Power Technical Assistance Partnership assessments between 2018 and 2024, can now apply for grants for implementation of assessment recommendations up 50% of qualifying* project costs with a maximum of $300,000 per manufacturer.
IMPORTANT: The grant program now operates on a rolling basis and applications may be submitted at any time through the year, with quarterly reviews.
*See Full Grant Solicitation for full qualification and selection details.
IAC Center University of Wisconsin, Milwaukee
Assessment Year 1992
Principal Product AUTOMOBILE SWITCHES
NAICS n/a
SIC 3679 - Electronic Components, Nec
Sales $1,000,000-$5,000,000
# of Employees 170
Plant Area (Sq.Ft.) 0
Annual Production 350,000 Pieces
Production Hrs. Annual 2,125
Location (State) IL
Source Yearly Cost Usage Unit Unit Cost
Electricity Usage $108,858 1,371,630 kWh $0.08
Natural Gas $13,436 3,587 MMBtu $3.75
TOTAL ENERGY COSTS $122,294
RECOMMENDED SAVINGS* $11,121 *Non-energy impacts
included in savings.
See recommendations below
IMPLEMENTED SAVINGS* $3,643
#|Description Savings
Cost
Status Electricity Usage Natural Gas Administrative Changes Electricity Usage Natural Gas Administrative Changes
$ kWh $ MMBtu $ $
01: 2.7261 INSTALL TIMERS AND/OR THERMOSTATS Savings:
$4,528
Cost:
$200
- - $4,528 1,207 - - -
-
kWh
$4,528
1,207
MMBtu
-
-
$
02: 2.7221 LOWER TEMPERATURE DURING THE WINTER SEASON AND VICE-VERSA Savings:
$783
Cost:
-
- - $783 209 - - -
-
kWh
$783
209
MMBtu
-
-
$
03: 2.3131 RESCHEDULE PLANT OPERATIONS OR REDUCE LOAD TO AVOID PEAKS Savings:
$1,055
Cost:
-
$1,055 - - - - - $1,055
-
kWh
-
-
MMBtu
-
-
$
04: 2.7142 UTILIZE HIGHER EFFICIENCY LAMPS AND/OR BALLASTS Savings:
$134
Cost:
$9
$617 7,913 - - $(-483) - $617
7,913
kWh
-
-
MMBtu
$(-483)
-
$
05: 2.6232 INSTALL SET-BACK TIMERS Savings:
$311
Cost:
$400
$311 3,810 - - - - $311
3,810
kWh
-
-
MMBtu
-
-
$
06: 2.7447 INSTALL VINYL STRIP / HIGH SPEED / AIR CURTAIN DOORS Savings:
$2,571
Cost:
$2,100
- - $2,571 685 - - -
-
kWh
$2,571
685
MMBtu
-
-
$
07: 2.2437 RECOVER WASTE HEAT FROM EQUIPMENT Savings:
$938
Cost:
-
- - $938 250 - - -
-
kWh
$938
250
MMBtu
-
-
$
08: 2.1311 REPLACE ELECTRICALLY-OPERATED EQUIPMENT WITH FOSSIL FUEL EQUIPMENT Savings:
$801
Cost:
-
$1,003 12,603 $(-202) (-54) - - $1,003
12,603
kWh
$(-202)
(-54)
MMBtu
-
-
$
TOTAL RECOMMENDED Savings:
$11,121
Cost:
$2,709
$2,986 24,326 $8,618 2,297 $(-483) - $2,986
24,326
kWh
$8,618
2,297
MMBtu
$(-483)
-
$
TOTAL IMPLEMENTED Savings:
$3,643
Cost:
$2,109
$617 7,913 $3,509 935 $(-483) - $617
7,913
kWh
$3,509
935
MMBtu
$(-483)
-
$
Savings
Cost
$ kWh $ MMBtu $ $
Electricity Usage Natural Gas Administrative Changes Electricity Usage Natural Gas Administrative Changes