Qualifying* small and medium-sized US manufacturers, that received IAC or Combined Heat and Power Technical Assistance Partnership assessments between 2018 and 2024, can now apply for grants for implementation of assessment recommendations up 50% of qualifying* project costs with a maximum of $300,000 per manufacturer.
IMPORTANT: The grant program now operates on a rolling basis and applications may be submitted at any time through the year, with quarterly reviews.
*See Full Grant Solicitation for full qualification and selection details.
IAC Center | University of Wisconsin, Milwaukee |
---|---|
Assessment Year | 2001 |
Principal Product | Biomedical Instruments |
NAICS | n/a |
SIC | 3826 - Analytical Instruments |
Sales | $50,000,000-$100,000,000 |
# of Employees | 220 |
Plant Area (Sq.Ft.) | 67,868 |
Annual Production | 2,400 Pieces |
Production Hrs. Annual | 2,750 |
Location (State) | WI |
Source | Yearly Cost | Usage | Unit | Unit Cost |
---|---|---|---|---|
Electricity Usage | $59,839 | 1,866,600 | kWh | $0.03 |
Electricity Demand | $34,140 | 3,996 | kW-months/year | $8.54 |
Electricity Fees | $6,745 | - | $ | - |
TOTAL ENERGY COSTS | $111,626 | |||
RECOMMENDED SAVINGS* | $114,618 | *Non-energy impacts included in savings. See recommendations below |
||
IMPLEMENTED SAVINGS* | $20,711 |
#|Description |
Savings Cost |
Status | Electricity Usage | Electricity Demand | Personnel Changes | Electricity Usage | Electricity Demand | Personnel Changes | |||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||
---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|
$ | kWh | $ | kW-months/year | $ | $ | ||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||
01: 4.448 INSTALL AUTOMATIC PART STORAGE / RETREVAL SYSTEM |
Savings: $82,500 Cost: $120,000 |
- | - | - | - | $82,500 | - |
- - kWh |
- - kW-months/year |
$82,500 - $ |
|||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||
02: 2.6231 UTILIZE CONTROLS TO OPERATE EQUIPMENT ONLY WHEN NEEDED |
Savings: $20,523 Cost: - |
$16,111 | 476,661 | $4,412 | 490 | - | - |
$16,111 476,661 kWh |
$4,412 490 kW-months/year |
- - $ |
|||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||
03: 2.4133 USE MOST EFFICIENT TYPE OF ELECTRIC MOTORS |
Savings: $7,035 Cost: $9,500 |
$5,522 | 163,374 | $1,513 | 168 | - | - |
$5,522 163,374 kWh |
$1,513 168 kW-months/year |
- - $ |
|||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||
04: 2.7142 UTILIZE HIGHER EFFICIENCY LAMPS AND/OR BALLASTS |
Savings: $3,569 Cost: $16,804 |
$1,777 | 52,583 | $1,792 | 199 | - | - |
$1,777 52,583 kWh |
$1,792 199 kW-months/year |
- - $ |
|||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||
05: 2.7142 UTILIZE HIGHER EFFICIENCY LAMPS AND/OR BALLASTS |
Savings: $188 Cost: $630 |
$147 | 4,354 | $41 | 5 | - | - |
$147 4,354 kWh |
$41 5 kW-months/year |
- - $ |
|||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||
06: 2.7135 INSTALL OCCUPANCY SENSORS |
Savings: $118 Cost: $450 |
$118 | 3,510 | - | - | - | - |
$118 3,510 kWh |
- - kW-months/year |
- - $ |
|||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||
07: 2.4146 USE ADJUSTABLE FREQUENCY DRIVE OR MULTIPLE SPEED MOTORS ON EXISTING SYSTEM |
Savings: $685 Cost: $3,600 |
$685 | 20,258 | - | - | - | - |
$685 20,258 kWh |
- - kW-months/year |
- - $ |
|||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||
TOTAL RECOMMENDED |
Savings: $114,618 Cost: $150,984 |
$24,360 | 720,740 | $7,758 | 862 | $82,500 | - | $24,360 720,740 kWh |
$7,758 862 kW-months/year |
$82,500 - $ |
|||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||
TOTAL IMPLEMENTED |
Savings: $20,711 Cost: $630 |
$16,258 | 481,015 | $4,453 | 495 | - | - | $16,258 481,015 kWh |
$4,453 495 kW-months/year |
- - $ |
|||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||
Savings Cost |
$ | kWh | $ | kW-months/year | $ | $ | |||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||
Electricity Usage | Electricity Demand | Personnel Changes | Electricity Usage | Electricity Demand | Personnel Changes |