Qualifying* small and medium-sized US manufacturers, that received IAC or Combined Heat and Power Technical Assistance Partnership assessments between 2018 and 2024, can now apply for grants for implementation of assessment recommendations up 50% of qualifying* project costs with a maximum of $300,000 per manufacturer.
IMPORTANT: The grant program now operates on a rolling basis and applications may be submitted at any time through the year, with quarterly reviews.
*See Full Grant Solicitation for full qualification and selection details.
IAC Center | University of Wisconsin, Milwaukee |
---|---|
Assessment Year | 2005 |
Principal Product | Paper Napkins and Plates |
NAICS | 322299 - All Other Converted Paper Product Manufacturing |
SIC | 2679 - Converted Paper Products, Nec |
Sales | <$500,000 |
# of Employees | 120 |
Plant Area (Sq.Ft.) | 300,000 |
Annual Production | 7,800 Tons |
Production Hrs. Annual | 6,000 |
Location (State) | WI |
Source | Yearly Cost | Usage | Unit | Unit Cost |
---|---|---|---|---|
Electricity Usage | $147,165 | 5,360,135 | kWh | $0.03 |
Electricity Demand | $112,375 | 12,771 | kW-months/year | $8.80 |
Electricity Fees | $62,286 | - | $ | - |
Natural Gas | $38,732 | 46,580 | MMBtu | $0.83 |
TOTAL ENERGY COSTS | $360,558 | |||
RECOMMENDED SAVINGS* | $166,407 | *Non-energy impacts included in savings. See recommendations below |
||
IMPLEMENTED SAVINGS* | $51,992 |
#|Description |
Savings Cost |
Status | Electricity Usage | Electricity Demand | Natural Gas | Personnel Changes | Electricity Usage | Electricity Demand | Natural Gas | Personnel Changes | |||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||
---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|
$ | kWh | $ | kW-months/year | $ | MMBtu | $ | $ | ||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||
01: 4.132 PURCHASE NEW EQUIPMENT TO REDUCE MATERIAL USE / COST |
Savings: $72,000 Cost: $85,000 |
- | - | - | - | - | - | $72,000 | - |
- - kWh |
- - kW-months/year |
- - MMBtu |
$72,000 - $ |
||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||
02: 2.4239 ELIMINATE OR REDUCE COMPRESSED AIR USAGE |
Savings: $42,415 Cost: $4,000 |
$21,537 | 745,174 | $20,878 | 2,257 | - | - | - | - |
$21,537 745,174 kWh |
$20,878 2,257 kW-months/year |
- - MMBtu |
- - $ |
||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||
03: 2.7142 UTILIZE HIGHER EFFICIENCY LAMPS AND/OR BALLASTS |
Savings: $33,445 Cost: $86,400 |
$20,392 | 705,600 | $13,053 | 1,411 | - | - | - | - |
$20,392 705,600 kWh |
$13,053 1,411 kW-months/year |
- - MMBtu |
- - $ |
||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||
04: 2.3131 RESCHEDULE PLANT OPERATIONS OR REDUCE LOAD TO AVOID PEAKS |
Savings: $12,421 Cost: - |
- | - | $12,421 | 1,343 | - | - | - | - |
- - kWh |
$12,421 1,343 kW-months/year |
- - MMBtu |
- - $ |
||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||
05: 2.6218 TURN OFF EQUIPMENT WHEN NOT IN USE |
Savings: $4,656 Cost: $500 |
- | - | - | - | $4,656 | 558 | - | - |
- - kWh |
- - kW-months/year |
$4,656 558 MMBtu |
- - $ |
||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||
06: 2.4236 ELIMINATE LEAKS IN INERT GAS AND COMPRESSED AIR LINES/ VALVES |
Savings: $1,470 Cost: $60 |
$1,470 | 50,868 | - | - | - | - | - | - |
$1,470 50,868 kWh |
- - kW-months/year |
- - MMBtu |
- - $ |
||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||
TOTAL RECOMMENDED |
Savings: $166,407 Cost: $175,960 |
$43,399 | 1,501,642 | $46,352 | 5,011 | $4,656 | 558 | $72,000 | - | $43,399 1,501,642 kWh |
$46,352 5,011 kW-months/year |
$4,656 558 MMBtu |
$72,000 - $ |
||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||
TOTAL IMPLEMENTED |
Savings: $51,992 Cost: $86,960 |
$21,862 | 756,468 | $25,474 | 2,754 | $4,656 | 558 | - | - | $21,862 756,468 kWh |
$25,474 2,754 kW-months/year |
$4,656 558 MMBtu |
- - $ |
||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||
Savings Cost |
$ | kWh | $ | kW-months/year | $ | MMBtu | $ | $ | |||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||
Electricity Usage | Electricity Demand | Natural Gas | Personnel Changes | Electricity Usage | Electricity Demand | Natural Gas | Personnel Changes |