Qualifying* small and medium-sized US manufacturers, that received IAC or Combined Heat and Power Technical Assistance Partnership assessments between 2018 and 2024, can now apply for grants for implementation of assessment recommendations up 50% of qualifying* project costs with a maximum of $300,000 per manufacturer.
IMPORTANT: The grant program now operates on a rolling basis and applications may be submitted at any time through the year, with quarterly reviews.
*See Full Grant Solicitation for full qualification and selection details.
IAC Center | Bradley University |
---|---|
Assessment Year | 2013 |
Principal Product | Electrical cabinets |
NAICS | 332439 - Other Metal Container Manufacturing |
SIC | 3499 - Fabricated Metal Products, Nec |
Sales | $10,000,000-$50,000,000 |
# of Employees | 57 |
Plant Area (Sq.Ft.) | 52,000 |
Annual Production | 4,000 Pieces |
Production Hrs. Annual | 4,160 |
Location (State) | IL |
Source | Yearly Cost | Usage | Unit | Unit Cost |
---|---|---|---|---|
Electricity Usage | $59,449 | 1,057,700 | kWh | $0.06 |
Electricity Demand | $51,664 | 3,780 | kW-months/year | $13.67 |
Electricity Fees | $408 | - | $ | - |
Natural Gas | $38,772 | 7,737 | MMBtu | $5.01 |
LPG | $3,209 | 109 | MMBtu | $29.39 |
TOTAL ENERGY COSTS | $153,502 | |||
RECOMMENDED SAVINGS* | $17,330 | *Non-energy impacts included in savings. See recommendations below |
||
IMPLEMENTED SAVINGS* | $12,975 |
#|Description |
Savings Cost |
Status | Electricity Usage | Electricity Demand | LPG | Electricity Usage | Electricity Demand | LPG | |||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||
---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|
$ | kWh | $ | kW-months/year | $ | MMBtu | ||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||
01: 2.4236 ELIMINATE LEAKS IN INERT GAS AND COMPRESSED AIR LINES/ VALVES |
Savings: $12,975 Cost: $200 |
$7,653 | 151,845 | $5,322 | 389 | - | - |
$7,653 151,845 kWh |
$5,322 389 kW-months/year |
- - MMBtu |
|||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||
02: 2.7142 UTILIZE HIGHER EFFICIENCY LAMPS AND/OR BALLASTS |
Savings: $1,306 Cost: $5,680 |
$760 | 14,318 | $546 | 37 | - | - |
$760 14,318 kWh |
$546 37 kW-months/year |
- - MMBtu |
|||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||
03: 2.3132 RECHARGE BATTERIES ON DURING OFF-PEAK DEMAND PERIODS |
Savings: $1,152 Cost: $30 |
- | - | $1,152 | 84 | - | - |
- - kWh |
$1,152 84 kW-months/year |
- - MMBtu |
|||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||
04: 2.4231 REDUCE THE PRESSURE OF COMPRESSED AIR TO THE MINIMUM REQUIRED |
Savings: $666 Cost: $25 |
$393 | 7,799 | $273 | 20 | - | - |
$393 7,799 kWh |
$273 20 kW-months/year |
- - MMBtu |
|||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||
05: 2.8227 ADJUST / MAINTAIN FORK LIFT TRUCKS FOR MOST EFFICIENT OPERATION |
Savings: $651 Cost: $2,300 |
$(-2,558) | (-50,752) | - | - | $3,209 | 109 |
$(-2,558) (-50,752) kWh |
- - kW-months/year |
$3,209 109 MMBtu |
|||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||
06: 2.4133 USE MOST EFFICIENT TYPE OF ELECTRIC MOTORS |
Savings: $354 Cost: $440 |
$138 | 2,735 | $216 | 16 | - | - |
$138 2,735 kWh |
$216 16 kW-months/year |
- - MMBtu |
|||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||
07: 2.4221 INSTALL COMPRESSOR AIR INTAKES IN COOLEST LOCATIONS |
Savings: $226 Cost: $700 |
$133 | 2,642 | $93 | 7 | - | - |
$133 2,642 kWh |
$93 7 kW-months/year |
- - MMBtu |
|||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||
TOTAL RECOMMENDED |
Savings: $17,330 Cost: $9,375 |
$6,519 | 128,587 | $7,602 | 553 | $3,209 | 109 | $6,519 128,587 kWh |
$7,602 553 kW-months/year |
$3,209 109 MMBtu |
|||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||
TOTAL IMPLEMENTED |
Savings: $12,975 Cost: $200 |
$7,653 | 151,845 | $5,322 | 389 | - | - | $7,653 151,845 kWh |
$5,322 389 kW-months/year |
- - MMBtu |
|||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||
Savings Cost |