Implementation Grant Funding Opportunity Open
IMPORTANT: The grant program operates on a rolling basis and applications may be submitted at any time, with quarterly reviews.
Learn More
Implementation Grant Funding Opportunity Open
Qualifying* small and medium-sized US manufacturers, that received IAC or Combined Heat and Power Technical Assistance Partnership assessments between 2018 and 2024, can now apply for grants for implementation of assessment recommendations up 50% of qualifying* project costs with a maximum of $300,000 per manufacturer.
IMPORTANT: The grant program now operates on a rolling basis and applications may be submitted at any time through the year, with quarterly reviews.
*See Full Grant Solicitation for full qualification and selection details.
IAC Center | San Francisco State University |
---|---|
Assessment Year | 1997 |
Principal Product | Pre-Engineered Metal Building Systems |
NAICS | n/a |
SIC | 3448 - Prefabricated Metal Buildings |
Sales | $10,000,000-$50,000,000 |
# of Employees | 134 |
Plant Area (Sq.Ft.) | 108,000 |
Annual Production | 24,000 Tons |
Production Hrs. Annual | 6,240 |
Location (State) | CA |
Source | Yearly Cost | Usage | Unit | Unit Cost |
---|---|---|---|---|
Electricity Usage | $182,865 | 2,243,845 | kWh | $0.08 |
Electricity Demand | $27,206 | 6,918 | kW-months/year | $3.93 |
Natural Gas | $16,156 | 3,163 | MMBtu | $5.11 |
LPG | $17,058 | 1,742 | MMBtu | $9.79 |
TOTAL ENERGY COSTS | $267,485 | |||
RECOMMENDED SAVINGS* | $72,525 | *Non-energy impacts included in savings. See recommendations below |
||
IMPLEMENTED SAVINGS* | $26,935 |
#|Description |
Savings Cost |
Status | Electricity Usage | Electricity Demand | Natural Gas | Solid Waste (non-haz) | Electricity Usage | Electricity Demand | Natural Gas | Solid Waste (non-haz) | |||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||
---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|
$ | kWh | $ | kW-months/year | $ | MMBtu | $ | lb | ||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||
01: 2.7142 UTILIZE HIGHER EFFICIENCY LAMPS AND/OR BALLASTS |
Savings: $8,912 Cost: $15,660 |
$7,673 | 94,080 | $1,239 | 315 | - | - | - | - |
$7,673 94,080 kWh |
$1,239 315 kW-months/year |
- - MMBtu |
- - lb |
||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||
02: 2.7134 USE PHOTOCELL CONTROLS |
Savings: $4,008 Cost: $4,000 |
$3,509 | 43,083 | $499 | 127 | - | - | - | - |
$3,509 43,083 kWh |
$499 127 kW-months/year |
- - MMBtu |
- - lb |
||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||
03: 2.4133 USE MOST EFFICIENT TYPE OF ELECTRIC MOTORS |
Savings: $904 Cost: $1,271 |
$772 | 9,379 | $132 | 34 | - | - | - | - |
$772 9,379 kWh |
$132 34 kW-months/year |
- - MMBtu |
- - lb |
||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||
04: 2.4236 ELIMINATE LEAKS IN INERT GAS AND COMPRESSED AIR LINES/ VALVES |
Savings: $5,248 Cost: $4,065 |
$4,426 | 54,220 | $822 | 209 | - | - | - | - |
$4,426 54,220 kWh |
$822 209 kW-months/year |
- - MMBtu |
- - lb |
||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||
05: 2.6218 TURN OFF EQUIPMENT WHEN NOT IN USE |
Savings: $1,606 Cost: $1,880 |
$1,506 | 18,464 | $100 | 25 | - | - | - | - |
$1,506 18,464 kWh |
$100 25 kW-months/year |
- - MMBtu |
- - lb |
||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||
06: 2.1332 CONVERT COMBUSTION EQUIPMENT TO BURN NATURAL GAS |
Savings: $6,415 Cost: $2,079 |
- | - | - | - | $6,415 | - | - | - |
- - kWh |
- - kW-months/year |
$6,415 - MMBtu |
- - lb |
||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||
07: 2.7133 USE SEPARATE SWITCHES ON PERIMETER LIGHTING WHICH MAY BE TURNED OFF WHEN NATURAL LIGHT IS AVAILABLE |
Savings: $3,636 Cost: $12,250 |
$3,210 | 39,273 | $426 | 108 | - | - | - | - |
$3,210 39,273 kWh |
$426 108 kW-months/year |
- - MMBtu |
- - lb |
||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||
08: 3.5316 CONTRACT A WOOD PALLET RECYCLING COMPANY |
Savings: $10,416 Cost: $250 |
- | - | - | - | - | - | $10,416 | - |
- - kWh |
- - kW-months/year |
- - MMBtu |
$10,416 - lb |
||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||
09: 3.5313 INCREASE AMOUNT OF WASTE RECOVERED FOR RESALE |
Savings: $979 Cost: $350 |
- | - | - | - | - | - | $979 | - |
- - kWh |
- - kW-months/year |
- - MMBtu |
$979 - lb |
||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||
10: 3.5313 INCREASE AMOUNT OF WASTE RECOVERED FOR RESALE |
Savings: $952 Cost: - |
- | - | - | - | - | - | $952 | - |
- - kWh |
- - kW-months/year |
- - MMBtu |
$952 - lb |
||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||
11: 3.1191 CHANGE PROCEDURES / EQUIPMENT / OPERATING CONDITIONS |
Savings: $1,394 Cost: - |
- | - | - | - | - | - | $1,394 | 2,526 |
- - kWh |
- - kW-months/year |
- - MMBtu |
$1,394 2,526 lb |
||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||
12: 3.2123 CONVERT TO HIGH VOLUME LOW PRESSURE (HVLP) PAINT GUNS |
Savings: $28,055 Cost: $100,000 |
- | - | - | - | - | - | $28,055 | 5,000 |
- - kWh |
- - kW-months/year |
- - MMBtu |
$28,055 5,000 lb |
||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||
TOTAL RECOMMENDED |
Savings: $72,525 Cost: $141,805 |
$21,096 | 258,499 | $3,218 | 818 | $6,415 | - | $41,796 | 7,526 | $21,096 258,499 kWh |
$3,218 818 kW-months/year |
$6,415 - MMBtu |
$41,796 7,526 lb |
||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||
TOTAL IMPLEMENTED |
Savings: $26,935 Cost: $9,545 |
$6,704 | 82,063 | $1,054 | 268 | $6,415 | - | $12,762 | 2,526 | $6,704 82,063 kWh |
$1,054 268 kW-months/year |
$6,415 - MMBtu |
$12,762 2,526 lb |
||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||
Savings Cost |
$ | kWh | $ | kW-months/year | $ | MMBtu | $ | lb | |||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||
Electricity Usage | Electricity Demand | Natural Gas | Solid Waste (non-haz) | Electricity Usage | Electricity Demand | Natural Gas | Solid Waste (non-haz) |