Implementation Grant Funding Opportunity Open
IMPORTANT: The grant program operates on a rolling basis and applications may be submitted at any time, with quarterly reviews.
Learn More
Implementation Grant Funding Opportunity Open
Qualifying* small and medium-sized US manufacturers, that received IAC or Combined Heat and Power Technical Assistance Partnership assessments between 2018 and 2024, can now apply for grants for implementation of assessment recommendations up 50% of qualifying* project costs with a maximum of $300,000 per manufacturer.
IMPORTANT: The grant program now operates on a rolling basis and applications may be submitted at any time through the year, with quarterly reviews.
*See Full Grant Solicitation for full qualification and selection details.
IAC Center | University of Florida |
---|---|
Assessment Year | 2023 |
Principal Product | Ophthalmic Medication |
NAICS | 339112 - Surgical and Medical Instrument Manufacturing |
SIC | 3841 - Surgical And Medical Instruments |
Sales | $100,000,000-$500,000,000 |
# of Employees | 500 |
Plant Area (Sq.Ft.) | 175,677 |
Annual Production | 65,000,000 Units |
Production Hrs. Annual | 8,760 |
Location (State) | FL |
Source | Yearly Cost | Usage | Unit | Unit Cost |
---|---|---|---|---|
Electricity Usage | $885,582 | 17,794,789 | kWh | $0.05 |
Electricity Demand | $414,289 | 30,331 | kW-months/year | $13.66 |
Electricity Fees | $214,588 | - | $ | - |
Natural Gas | $159,004 | 57,394 | MMBtu | $2.77 |
TOTAL ENERGY COSTS | $1,900,581 | |||
RECOMMENDED SAVINGS* | $1,840,708 | *Non-energy impacts included in savings. See recommendations below |
||
IMPLEMENTED SAVINGS* | $1,710,305 |
#|Description |
Savings Cost |
Status | Electricity Usage | Electricity Demand | Electricity Fees | Natural Gas | Ancillary Material Cost | Electricity Usage | Electricity Demand | Electricity Fees | Natural Gas | Ancillary Material Cost | |||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||
---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|
$ | kWh | $ | kW-months/year | $ | $ | $ | MMBtu | $ | $ | ||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||
01: 2.3417 USE WASTE HEAT WITH A CLOSED-CYCLE GAS TURBINE-GENERATOR SET TO COGENERATE ELECTRICITY AND HEAT |
Savings: $920,434 Cost: $2,793,000 |
$889,739 | 17,794,789 | $344,207 | 25,200 | - | - | $(-327,887) | (-118,328) | $14,375 | - |
$889,739 17,794,789 kWh |
$344,207 25,200 kW-months/year |
- - $ |
$(-327,887) (-118,328) MMBtu |
$14,375 - $ |
|||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||
02: 2.3113 MAKE ICE DURING OFF PEAK HOURS FOR COOLING |
Savings: $505,092 Cost: $2,115,660 |
$306,633 | 6,132,668 | - | - | $198,459 | - | - | - | - | - |
$306,633 6,132,668 kWh |
- - kW-months/year |
$198,459 - $ |
- - MMBtu |
- - $ |
|||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||
03: 2.3191 USE DEMAND CONTROLLER OR LOAD SHEDDER |
Savings: $130,403 Cost: $95,736 |
$88,974 | 1,779,479 | $41,429 | 3,033 | - | - | - | - | - | - |
$88,974 1,779,479 kWh |
$41,429 3,033 kW-months/year |
- - $ |
- - MMBtu |
- - $ |
|||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||
04: 2.6231 UTILIZE CONTROLS TO OPERATE EQUIPMENT ONLY WHEN NEEDED |
Savings: $71,810 Cost: $25,340 |
$71,810 | 1,436,203 | - | - | - | - | - | - | - | - |
$71,810 1,436,203 kWh |
- - kW-months/year |
- - $ |
- - MMBtu |
- - $ |
|||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||
05: 2.7142 UTILIZE HIGHER EFFICIENCY LAMPS AND/OR BALLASTS |
Savings: $42,787 Cost: $43,077 |
$30,363 | 607,262 | $12,424 | 910 | - | - | - | - | - | - |
$30,363 607,262 kWh |
$12,424 910 kW-months/year |
- - $ |
- - MMBtu |
- - $ |
|||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||
06: 2.5122 REPLACE HIGH RESISTANCE DUCTS, PIPES, AND FITTINGS |
Savings: $18,200 Cost: $14,400 |
$18,200 | 364,000 | - | - | - | - | - | - | - | - |
$18,200 364,000 kWh |
- - kW-months/year |
- - $ |
- - MMBtu |
- - $ |
|||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||
07: 2.2615 CLEAN CONDENSER TUBES |
Savings: $15,589 Cost: - |
$15,589 | 311,786 | - | - | - | - | - | - | - | - |
$15,589 311,786 kWh |
- - kW-months/year |
- - $ |
- - MMBtu |
- - $ |
|||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||
08: 2.1213 DIRECT WARMEST AIR TO COMBUSTION INTAKE |
Savings: $13,274 Cost: $30,000 |
- | - | - | - | - | - | $13,274 | 4,792 | - | - |
- - kWh |
- - kW-months/year |
- - $ |
$13,274 4,792 MMBtu |
- - $ |
|||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||
09: 2.4239 ELIMINATE OR REDUCE COMPRESSED AIR USAGE |
Savings: $5,438 Cost: - |
$5,438 | 108,767 | - | - | - | - | - | - | - | - |
$5,438 108,767 kWh |
- - kW-months/year |
- - $ |
- - MMBtu |
- - $ |
|||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||
10: 2.7245 USE DIRECT AIR SUPPLY TO EXHAUST HOODS |
Savings: $5,304 Cost: $4,300 |
$5,304 | 106,071 | - | - | - | - | - | - | - | - |
$5,304 106,071 kWh |
- - kW-months/year |
- - $ |
- - MMBtu |
- - $ |
|||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||
11: 2.1113 REDUCE COMBUSTION AIR FLOW TO OPTIMUM |
Savings: $4,770 Cost: $2,800 |
- | - | - | - | - | - | $4,770 | 1,722 | - | - |
- - kWh |
- - kW-months/year |
- - $ |
$4,770 1,722 MMBtu |
- - $ |
|||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||
12: 2.1222 INSTALL TURBULATORS |
Savings: $4,595 Cost: $7,500 |
- | - | - | - | - | - | $4,595 | 1,659 | - | - |
- - kWh |
- - kW-months/year |
- - $ |
$4,595 1,659 MMBtu |
- - $ |
|||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||
13: 2.7273 INSTALL DESICCANT HUMIDITY CONTROL SYSTEM |
Savings: $4,532 Cost: $754 |
$4,532 | 90,639 | - | - | - | - | - | - | - | - |
$4,532 90,639 kWh |
- - kW-months/year |
- - $ |
- - MMBtu |
- - $ |
|||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||
14: 2.7233 USE PROPERLY DESIGNED AND SIZED HVAC EQUIPMENT |
Savings: $4,316 Cost: $3,069 |
$4,316 | 86,326 | - | - | - | - | - | - | - | - |
$4,316 86,326 kWh |
- - kW-months/year |
- - $ |
- - MMBtu |
- - $ |
|||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||
15: 2.7135 INSTALL OCCUPANCY SENSORS |
Savings: $2,868 Cost: $9,968 |
$2,868 | 57,363 | - | - | - | - | - | - | - | - |
$2,868 57,363 kWh |
- - kW-months/year |
- - $ |
- - MMBtu |
- - $ |
|||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||
16: 2.7272 INSTALL HEAT PIPES / RAISE COOLING SETPOINT |
Savings: $2,322 Cost: - |
$2,322 | 46,443 | - | - | - | - | - | - | - | - |
$2,322 46,443 kWh |
- - kW-months/year |
- - $ |
- - MMBtu |
- - $ |
|||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||
17: 4.661 LEVEL ZERO – INSTALL CONTROL SYSTEMS FOR EXISTING EQUIPMENT |
Savings: $88,974 Cost: $10,000 |
$88,974 | 1,779,479 | - | - | - | - | - | - | - | - |
$88,974 1,779,479 kWh |
- - kW-months/year |
- - $ |
- - MMBtu |
- - $ |
|||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||
TOTAL RECOMMENDED |
Savings: $1,840,708 Cost: $5,155,604 |
$1,535,062 | 30,701,275 | $398,060 | 29,143 | $198,459 | - | $(-305,248) | (-110,155) | $14,375 | - | $1,535,062 30,701,275 kWh |
$398,060 29,143 kW-months/year |
$198,459 - $ |
$(-305,248) (-110,155) MMBtu |
$14,375 - $ |
|||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||
TOTAL IMPLEMENTED |
Savings: $1,710,305 Cost: $5,059,868 |
$1,446,088 | 28,921,796 | $356,631 | 26,110 | $198,459 | - | $(-305,248) | (-110,155) | $14,375 | - | $1,446,088 28,921,796 kWh |
$356,631 26,110 kW-months/year |
$198,459 - $ |
$(-305,248) (-110,155) MMBtu |
$14,375 - $ |
|||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||
Savings Cost |
$ | kWh | $ | kW-months/year | $ | $ | $ | MMBtu | $ | $ | |||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||
Electricity Usage | Electricity Demand | Electricity Fees | Natural Gas | Ancillary Material Cost | Electricity Usage | Electricity Demand | Electricity Fees | Natural Gas | Ancillary Material Cost |